P.O.Box 368, Union, NJ 07083-0368, 908-687-7810, 800-327-2443, Fax: 908-687-8860

PAIGEWEBHEADER.GIF (3336 bytes)
P7001D-Rev 2
                  
UNDERGROUND  FEEDER CABLE (UF)
INSULATION: POLYVINYL CHLORIDE
P7264D
SIZE: 14 AWG - 4/0 AWG Ullogo.gif (224 bytes)
1.0 SCOPE: GroupImage
*Current carrying capacity based on not more
than 3 conductors in raceway or cable or
direct burial (at room temperature of 30°C)
1.1 This specification covers the construction requirements for Underground Feeder Cable, Type UF, for use in
accordance with the National Electrical Code or operation at a potential of 600 Volts or less and at a temperature
of 60°C or less. UL listed.
2.0 CONSTRUCTION:
2.1 Conductor: .
Soft drawn bare copper meeting the requirements of ASTM specification B-3 or B-8
2.2 Temperature Rating:
-10°C +60°C.
2.3 Insulation:
Polyvinyl chloride, 60°C rated conforming to UL Standards 493 and 83.
2.4 Manufacturer's Identification:
Surface marked with Paige-Electric, voltage rating, size and type, and UL file number.
2.5 Underwriters' Laboratories Approval:
All cables shall be tested physically and electrically in accordance with UL Standard 493, and 83
(paragrahs 28.1, 29.1 and 29.2). All reels and
cartons bear UL labels